Turck LS-551-0500-LIU22PN8X-H1151

מאפיינים מרכזיים

With the new microwave sensors of the LS-5 series, levels of liquids can be continuously detected. Two or four switching outputs and one analog output enable simultaneous detection of limit values and the actual liquid level. The devices are insensitive to adhesive and foam media.

The LS-5 sensors offer optimum operation in metallic tanks but can also be used in nonmetallic vessels by means of a coaxial tube.

  • Level detection and continuous level measurement
  • Easy to service and quick to deploy without calibration
  • Very flexible since probes can be shortened
  • Easy installation thanks to compact, rotatable housing with display
  • Process temperature up to 100 °C
  • Process pressure up to 10 bar
  • Small blind zones, ideal for small containers
  • Coaxial tube available for non-metallic tanks
  • IO-Link 1.1
  • 12…30 VDC
  • 1 × analog output 4… 20 mA/0… 10 V (automatic switchover depending on load)
  • 1 × transistor output (PNP) or IO-Link
  • 1 × transistor output (PNP/NPN switchable))
  • Process connection G3/4" male thread
  • Probe length 500 mm

General data

EAN 4047101554458
Customs tariff number 90261029000
Country of origin DE
Weight 860 g

Technical Data

Detection type medium contact
Medium liquids
Measuring principle Guided microwave
Process connection G 3/4" male thread
Probe length (L) 500  mm
Operating voltage 12…30 VDC
Output function NO/NC, PNP/NPN, analog output
Voltage output 0…10 V
Current output 4…20 mA
Communication protocol IO-Link
Electrical connection Connectors, M12 × 1
Materials (contact with media) Stainless steel 1.4404 (AISI 316L), PTFE, FKM
Housing material Plastic, PBT
Medium temperature -20…+100 °C
Pressure resistance -1…10 bar
Ambient temperature -20…+60 °C
Protection class IP67