Fluke 1760 – מקליט איכות חשמל תלת פאזי

מאפיינים מרכזיים

Fluke 1760 בעל תאימות מלאה ל- IEC 61000-4-30 Class-A, מושלם לניתוח איכות חשמל ובדיקות תאימות עקביות.

  • EN50160
  • GPS
  • זיכרון

מדידות:

  • Main Signaling
  • PF
  • THD
  • איזון פאזות
  • אינטר הרמוניות
  • אנרגיה
  • הספק
  • הרמוניות זרם
  • הרמוניות מתח
  • זרם
  • מתח
  • פליקרים
  • שקיעות ועליות מתח
  • תדר

Number of Phases

  • תלת פאזי
Intrinsic uncertainty refers to reference conditions and is guaranteed for two years
Quality system developed, manufactured as per ISO 9001: 2000
Environment conditions Operating temp. range: 0 °C to +50 °C
Working temp. range: -20 °C to +50 °C
Storage temp. range: 20 °C to +60 °C
Reference temperature: 23 °C ± 2 K
Climatic class: B2 (IEC 654-1), -20 °C to +50 °C; -4 °F to +122 °F
Max. operating altitude: 2000 m: max. 600 V CAT IV*, power supply: 300 V CAT III 5000 m: max 600 V CAT III*, power supply: 300 V CAT II
* depending on sensor
Reference conditions Environment temp.: 23 °C ± 2 K ; 74°F ± 2 K
Power supply: 230 V ± 10 %
Power frequency: 50 Hz / 60 Hz
Signal: declared input voltageUdin
Averaging: 10 minute intervals
Housing insulated, robust plastics housing
EMC Emission: Class-A as per IEC/EN 61326-1
Immunity: IEC/EN 61326-1
Power supply Range: AC: 83 V to 264 V, 45 to 65 Hz
DC: 100 V to 375 V
Safety: IEC/EN 61010-1 2nd edition
300 V CAT III
Power consumption: max. 54VA
Battery pack: NIMH, 7.2 V, 2.7 Ah
In case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns. The battery can be replaced by the user.
Display Fluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
PowerLED: • Permanent light: normal power supply from mains.
• OFF: supply via internal accumulator in case of a power failure.
ChannelLEDs 3-color LEDs per channel for:
• overload condition
• under load condition
signal level in nominal range
Data memory 2 GB Flash memory depending on model
Memory model Linear
Interfaces Ethernet (100MB/s), compatible to Windows® 98/ME/NT/2000/XP RS 232, external modem via RS 232
Baud rate for RS 232 9600 Baud to 115 kBaud
Dimensions 325 mm x 300 m x 65 mm; 2.8 x 11.8 x 2.6 in. (H x W x D)
Weight appr. 4.9 kg (without accessories)
Warranty 2 years
Calibration interval 1 year recommended for Class-A, otherwise 2 years